Percolation and soakaway tests
A percolation test measures how quickly water drains away into the ground on your site. Building control may ask for the result to show that a soakaway for rainwater, or a drainage field for a septic tank or small treatment plant, will work. The two uses are tested and judged differently, so it helps to know which one you need.
This guide covers the rules in England. See Wales, Scotland and Northern Ireland.
- drainage and ground testing specialists listed
- 61
- verified listings
- 2
- regulation or standard
- Part H
- region pages
- 12
61 drainage and ground testing specialists listed across the UK
Featured (paid) listings first, then A–Z · How we check listings
London (12) South East (17) East of England (8) South West (12) West Midlands (11) East Midlands (12) Yorkshire and the Humber (10) North West (10) North East (9) Wales (8) Scotland (10) Northern Ireland (7)
National providers (23)
Below Ground Solutions Ltd
Based in Taunton, Somerset · Covers UK-wide for percolation testsBetts Associates (Betts Hydro)
Based in Sealand, Flintshire, Wales · Covers UK-wideCastledine Environmental
Based in Leeds, West Yorkshire · Covers Yorkshire and the Humber; also works nationallyCreate Consulting EngineersVerified
Based in Norwich, Norfolk (also London, Glasgow, Chelmsford, Milton Keynes) · Covers UK-wide (England and Scotland, from five offices)Earth Environmental & Geotechnical
Based in Stockport, Greater Manchester · Covers UK-wideEarth Science Partnership Ltd
Based in Taff's Well, Cardiff · Covers Wales, England, Scotland, Northern Ireland and IrelandG&J Geoenvironmental Consultants Ltd
Based in Barrow-upon-Soar, Leicestershire · Covers Throughout the UK from a Midlands baseGeocon Site Investigations Ltd
Based in Marple, Stockport · Covers Nationwide; Newcastle office covers North East, North Yorkshire, Humberside and ScotlandGeoinvestigate
Based in Newcastle upon Tyne, Tyne and Wear · Covers Newcastle, County Durham, Northumberland and across the UK; head office in North YorkshireGeoSmart Information
Based in Shrewsbury, Shropshire · Covers Not explicitly stated; serves planners, architects and developers nationallyGeosphere Environmental Ltd
Based in Brightwell, Suffolk · Covers Nationwide; most work in Suffolk, Essex, Norfolk, London, Bedfordshire and KentGRM Development Solutions
Based in Burton-on-Trent, Staffordshire · Covers Across the UKIan Farmer Associates (1998) Ltd
Based in Washington, Tyne and Wear · Covers Throughout the UK from hubs in Glasgow, Washington, Warrington, Coventry and Hemel HempsteadJNP Group
Based in Amersham, Buckinghamshire (offices across the UK) · Covers National coverage; offices in Amersham, Belfast, Brighouse, Bristol, Hartlepool, Sheffield and WarwickJomas Associates
Based in Uxbridge, London · Covers Nationwide; names London, Surrey, Kent and WalesMicro Geotechnical Ltd
Based in Hevingham, Norfolk · Covers NationwidePRP UK Ltd
Based in Enderby, Leicester · Covers Across the UK; offices in Leicester, Northampton and LondonSevenoaks Environmental Consultancy Ltd
Based in Pembury, Kent · Covers South East including London and the Home Counties; nationwide supportSolmek
Based in Stockton-on-Tees, County Durham · Covers Across the UK; offices in Stockton, Chesterfield, Glasgow and ReadingSouthwest Environmental Limited
Based in Taunton, Somerset · Covers UK-wide, with offices in Taunton, Exeter, Plymouth, Bristol, London, Manchester and EdinburghSub Surface Ltd
Based in Preston, Lancashire · Covers Nationwide from offices in Preston, Ossett, Tipton and High WycombeTwo different tests
Soakaway (infiltration) test
Checks whether the ground can take rainwater from roofs and hard surfaces, so a soakaway can be sized and sited. Requirement H3 of the Building Regulations (England and Wales) asks for adequate provision to carry rainwater from the roof and to drain paved areas around the building.
Percolation test for a drainage field
Used where wastewater from a septic tank or small treatment plant is discharged to the ground. The result is an average percolation value (Vp), used to size the drainage field.
When is one likely to be needed?
- New homes or extensions with no surface water sewer. Requirement H3 lists where rainwater must go, in order of priority: a soakaway or other infiltration system first, then a watercourse, then a sewer, each only where the option before it is not reasonably practicable.
- New homes with no mains drains. A septic tank or treatment plant that discharges to the ground normally needs a percolation test to show the ground is suitable. Approved Document H says a drainage field should only be used where the average Vp is between 12 and 100.
- Larger paved areas, new outbuildings and driveways that add enough run-off to need a proper soakaway or drainage design.
- A planning condition asking for a drainage strategy, which may include test results.
How a test works
A tester digs trial pits at the depth where the soakaway or drainage field would sit, fills them with water, and records how quickly the level falls. The result is an infiltration rate for the ground. It is then used to work out how big the soakaway or drainage field needs to be, so tests are done before the drainage is designed.
For a drainage field, Approved Document H sets out the method: a 300 mm square hole dug to 300 mm below the proposed pipe, soaked overnight, then refilled and timed as the water drops from 75% to 25% full. That time, divided by 150, gives Vp, the average seconds for the water to fall 1 mm. The test is repeated at least three times across at least two holes and averaged. A trial hole is also dug to check that groundwater does not rise to within 1 m of the pipe.
Tests are usually done in dry weather and, for a site with different soils, in more than one place. Rock, clay or a high water table can make a site unsuitable for infiltration, in which case the designer needs a different solution, such as discharge to a watercourse or sewer.
Things to check early
- Distances. Approved Document H says a drainage field should be at least 15 m from any building, and building control bodies expect soakaways to be kept clear of foundations too, so check the distances before you dig.
- Whether you need other consents. In England, a septic tank or small treatment plant that discharges to the ground must either meet the Environment Agency’s general binding rules (for example, no more than 2,000 litres a day and not in a groundwater source protection zone 1) or have an environmental permit. The rules also say a new system needs building regulations approval. Building near a public sewer may need the sewerage undertaker’s agreement.
- Whether the test result needs to be submitted with a full plans application or only made available to the building control officer on request.
In Wales, Scotland and Northern Ireland
This guide describes the rules in England. Building regulations are devolved, so here is how percolation and soakaway tests works in the rest of the UK.
Wales publishes its own version of Approved Document H. Since 7 January 2019, a new development of more than one dwelling, or with a construction area of 100 m² or more, also needs its surface water drainage approved by the council’s SuDS Approving Body (SAB) before work starts, separately from planning permission.
In Scotland, drainage is covered by Section 3 (Environment) of the building standards technical handbook: standard 3.7 for wastewater drainage and 3.8 and 3.9 for private treatment plants, septic tanks and infiltration fields. A septic tank or package treatment plant needs authorisation from SEPA. Check with your council’s building standards team.
In Northern Ireland, drainage is covered by Technical Booklet N. A septic tank or treatment plant discharging to a waterway or to the ground needs consent from the Northern Ireland Environment Agency under the Water (Northern Ireland) Order 1999, and NIEA asks for percolation test results where discharge to the ground is proposed.
Common questions
What is a percolation test?
A field test that measures how quickly water soaks into the ground. The result shows whether a soakaway or septic tank drainage field is likely to work, and how big it needs to be.
Is a percolation test the same as a soakaway test?
They use a similar idea but are not the same. A soakaway test is for rainwater drainage. A percolation test, as the term is used for septic tanks, is for dispersing treated wastewater. Check which one your building control body or designer is asking for.
Do I need a percolation test for an extension?
Often not, if rainwater already goes to an existing sewer or soakaway that can take the extra run-off. You are more likely to need one if you have no sewer to connect to, or if the extension adds a lot of roof or paving.
What if the ground fails the test?
A failed test means water drains too slowly or too quickly for a standard design. For a drainage field, Approved Document H says values of Vp outside 12 to 100 are unlikely to treat the effluent properly. Your designer may suggest a different system, or another way of discharging water, such as to a watercourse.
How long does a test take?
The digging and testing is usually a short site visit, followed by a written result. Allow extra time for booking, for weather, and for the drainage to be designed from the result.
Who can do the test?
Drainage specialists, groundworks firms and ground investigation or environmental consultants offer it. Ask whether their report will be accepted by your building control body.
Sources
The rules and dates in this guide were checked against these pages on 12 October 2026. They are independent of us and may change, so check the current version before you rely on it.
- The Building Regulations 2010, Schedule 1 (requirements H1 to H6)
- Approved Document H: Drainage and waste disposal, 2015 edition (PDF)
- General binding rules: small sewage discharge to the ground (GOV.UK)
- Approved Document H: drainage and waste disposal (Welsh Government)
- Implementation of Schedule 3 to the Flood and Water Management Act 2010: FAQs (Welsh Government, PDF)
- Building standards technical handbook 2022, domestic: 3.7 Wastewater drainage (Scottish Government)
- Private sewerage (mygov.scot)
- Regulating water discharges (DAERA, Northern Ireland)
New to the jargon? See our glossary of terms, from air permeability to TrustMark.